76

OID

Name

Model

MAX-ACCESS

Comment

1

ident

ID Group

1.1.0

identSWinitVersion

String(2)

read-only

OS Version

1.2.0

identSWAgentVersion

String(3)

read-only

Application Version

1.3.0

idensHWVersion

String(3)

read-only

Hardware Version

4

monitor

Monitor Group

4.1

pingServer

ping monitoring setting

4.1.1.0

pingServerNumEntries

INTEGER

read-only

Ping monitoring count

4.1.2.0

pingServerTable

not-accessible ping monitoring table

4.1.2.1.0

pingServerTableEntry

not-accessible

4.1.2.1.1.(index) pingServerTableIndex

INTEGER

read-only

ping monitoring index

4.1.2.1.2.(index) pingServerName

STRING(31)

read-only

ping monitor name

4.1.2.1.3.(index) pingServerAlertValue

INTEGER{ normal(1),

occurred(2) }

read-only

ping monitor condition

normal(1), event occurred(2)

4.1.2.1.4.(index) pingServerIpAddress

STRING(63)

read-only

ping monitoring address

4.3

logDump

log setting

4.3.1.0

logDumpEventlog1

OBJECT IDENTFIER

read-only

event log from 1 to 85

4.3.2.0

logDumpEventlog2

OBJECT IDENTFIER

read-only

event log from 86 to 170

4.3.3.0

logDumpEventlog3

OBJECT IDENTFIER

read-only

event log from 171 to 255

5.1

controlLight

signal tower control

5.1.1.0

controlLightNumEntries

INTEGER

read-only

count of control entries

5.1.2.0

controlLightTable

not-accessible signal tower table

5.1.2.1.0

controlLightTableEntry

not-accessible

5.1.2.1.1.(index) controlLightDeviceColor

INTEGER {red(1), am-

ber(2), green(3), blue(4),

clear(5), buzzer(6) }

read-only

signal tower color

R(1)/Y(2)/G(3)/B(4)/C(5)/Buz(6)

5.1.2.1.2.(index) controlLightControlState

INTEGER {turn-off(1),

turn-ON(2), blinking-pat-

-pat-

tern(3), nop(4), blinking-

patern2(5), sound-

pattern4(6) }

read-write

Signal Tower Status: lights and buzzer

off(1)/lighting and buzzer synchronized

with light pattern1(2)/flashing pattern1

and buzzer synchronized with light

pattern2(3)/no change(4)/flashing pat-

tern2 and buzzer synchronized with light

pattern3(5)/buzzer synchronized with light

pattern 4(6). controlLightControlTimer is

set by entering values above zero.

5.1.2.1.3.(index) controlLightControlTimer

INTEGER(-1,99)

read-write

A preset value is decremented for every

second until it is 0, then it changes to the

status designated by the controlLightCon-

trolState.

5.1.2.1.4.(index) controlLightCurrentState

INTEGER { off(1), on(2),

blinking-pattern1(3),

blinking-pattern2(4),

sound-pattern4(5) }

read-only

The present status is displayed.

lights and buzzer off(1)/lighting and buzzer

synchronized with light pattern1(2)/flash-

ing pattern1 and buzzer synchronized

with light pattern2(3)/flashing pattern2 and

buzzer synchronized with light pattern3(4)/

buzzer synchronized with light pattern4(5)

5.1.3.0

controlLightSnmpClear

INTEGER{ execute(1),

nop(0) }

read-write

execute(1) setup will clear the Signal

Tower operation.

6

Trap

6.1

trapPatliteAlarmAdded

OBJECT-IDENTIFIER

not-accessible When an abnormality in the PING occurs

6.2

trapPatliteAlarmRemoved

OBJECT-IDENTIFIER

not-accessible When an abnormality in the PING is

restored

6.3

trapPatliteTrapReceived

OBJECT-IDENTIFIER

not-accessible When a trap is received

6.4

trapPatliteClearExecuted

OBJECT-IDENTIFIER

not-accessible When the clear button is pushed

6.5

trapPatliteRshExecuted

OBJECT-IDENTIFIER

not-accessible When an RSH command is executed

6.6

trapPatliteAppMonitorAlarmAdded

OBJECT-IDENTIFIER

not-accessible When an abnormality in the application

occurs

6.7

trapPatliteAppMonitorAlarmRemoved OBJECT-IDENTIFIER

not-accessible When an abnormality in the application is

restored

6.8

trapPatliteTestSwExecuted

OBJECT-IDENTIFI-

ER

not-accessi-

ble

When the test switch is pushed