Setting the analog signal source to flow, Using analog output for heating and cooling – Sterlco M2B+ Controller User Manual

Page 31

Advertising
background image

31 of 68

Setting the Analog Signal Source to FLOW

If the analog signal source is set to “FLOW,” follow steps 1 through 15 on page 30, and then
complete the following procedure:

1. Press the Index button until the display reads “Remote Input.”
2. Use the Up and Down buttons to change the value to “FLOW.”
3. Press the Enter button to accept the value.
4. Press the Index button until the display reads “Remote Signal.” Do not alter this

value; use the default setting.

5. Press the Enter button to accept the default setting.
6. Press the Index button until the display reads “Remote Flowslo=Minimum Flow

Value.”

7. Use the Up and Down buttons to change the value to 0.
8. Press the Enter button to accept the value.
9. Press the Index button until the display reads “Remote Flowshi=Maximum Flow

Value.”

10. Press the Enter button to accept the default value.
11. Press the Alarm Silence button to return to Running mode.
12. Press the Index button two times to access the Secondary menu.
13. Press the Enter button.
14. Press the Index button until the display reads “Remote Input.”
15. Use the Up and Down buttons to select “OFF.”
16. Press the Enter button to accept the value.
17. Press the Alarm Silence button to return to Running mode.

Using Analog Output for Heating and Cooling

This feature is typically set up at the factory, but it can also be installed as a retrofit in the
field. It is used to control a modulating valve or heating SCR proportionally. The analog
signal can be configured to be 0-20mA, 4-20Ma, 0-5VDC, 1-5VDC, 0-10VDC, and 2-
10VDC. Inserting the card into header “J5” for cooling or “J6” for heating automatically
configures the controller to direct its outputs through these boards.

Use the following procedure to set up the analog outputs:

1. Insert the analog card (P/N 691-00537-00) into the appropriate header.
2. Press the Index button two times to access the Secondary menu.
3. Press the Enter button.
4. Press the Index button until the display reads “Cool Output” or “Heat Output.”
5. Use the Up and Down buttons to select the analog signal type.
6. Press the Enter button to accept the value.
7. Press the Alarm Silence button to return to Running mode.