Bit 5 -Alarm, Low Temperature
Bit 7 -Alarm, Low Pressure
Bit 14 -Alarm, Phase Reversed or Lost

(44H)

Status, machine 2 poll-Returns the status of the machine as 16 flag bits in open

format. The following bits are supported. The rest are set to 0.

Bit 0 -Processing
Bit 1 -Alarm, System
Bit 2 -Alarm, Process
Bit 3 -Alarm, Machine
Bit 4 -Fault, Sensor, Delivery
Bit 5 -Fault, Sensor, Return

(48H)

Mode, Machine Poll-Returns the current status of temperature control unit if the

machine is On (1) or Off{O).

(49H) Mode, Machine Select-Commands the temperature control unit to turn On(1) or

Off(D)

Bit 0- Machine On/Off, Bit 1 -Alarm Acknowledge

(70H) Temperature, to process poll-Returns the delivery temperature in numeric format.

(72H) Temperature, from process poll -Returns the return temperature in numeric

format.