5-10 Programming Ramp/Soak

The controller has a 16-segment, front-face programmable Ramp/Soak feature. Unused
alarms can be programmed as a segment.

Do not attempt to auto-tune the controller during a ramp/soak program. The

Tune button will not function during this process.

Instead of requiring the operator to calculate an approach rate, the controller does the
calculation automatically. The operator needs to program the target setpoint and the time
desired to reach that setpoint. When the controller executes the ramp segment, it calculates
the ramp required to reach the process temperature from starting setpoint to the programmed
setpoint in the time allowed. (See Figure 2 for sample ramp/soak program.)

Dwells (or soaks) are ramp segments with target setpoint equal to starting process
temperature. This allows for multistage ramps without wasting intermediate soak steps.

Before programming Ramp/Soak, evaluate your program on paper.

Test any program for best results before running production material.

Make sure to run auto-tune before operating Ramp/soak because

Ramp functions will interfere with the operation of the auto-tune

Segment Prompt

Function

Time (min.)

Setpoint, ºF

1TI

1st Event

1

1SP

50

2TI

2nd Event

2

2SP

150

3TI

3rd Event

2

3SP

150

4TI

4th Event

2

4SP

100

5TI

5th Event

1

5SP

100

6TI

6th Event

2

5SP

50

7TI

Un-Used

0

7SP

Hold Last Setpoint

50

Un-Used

GTI

Un-Used

0

GSP

50

END

Stay at present setpoint (GSP)

HOLD

END

Revert to SP1 value

SETP

END

Repeat program at 1TI

LOOP
















Figure 2: Sample Ramp Soak Program