Use the following procedure to program the Ramp/Soak functions:

Starting Ramp/Soak Programming:

1. Press the Index button two times to access the Secondary menu.
2. Press the Enter button.
3. Press the Index button until the display reads “Prog Ramp/Soak.”
4. Use the Up and Down buttons to change the parameter to “On.”
5. Press the Enter button to accept the change.
6. Press the Index button one time to access the “Prog Values” parameter.
7. Press the Enter button.
8. Use the Up and Down buttons to change the parameter to “On.”
9. Press the Enter button to accept the change.
10. Press the Index button until the display reads “Prog Time Base.”
11. Press the Enter button.
12. Use the Up and Down buttons to change the time base for each segment. Choose

seconds or minutes. (1s=seconds, 60s=minutes.)

13. Press the Enter button to accept the change.

Programming the Ramp/Soak Segments:

1. Press the Index button one time to access the “Seg 1 Time” parameter.
2. Press the Enter button.
3. Use the Up and Down buttons to change the length of time for Segment 1.
4. Press the Enter button to save the segment time for Segment 1.
5. Press the Index button one time to access the “Seg 1 SetPoint” parameter.
6. Press the Enter button.
7. Use the Up and Down arrows to set the desired setpoint at the end of Segment 1.
8. Press the Enter button to save the setpoint for Segment1.
9. Repeat steps 1-8 for each of the 16 segments. Segment time should be set to 0 for

unused segments.

Finishing the Ramp/Soak Programming:

1. Press the Index button until the display reads “Prog End.”
2. Press the Enter button.
3. Use the Up and Down buttons to change the value for the desired reaction at the end

of the program. “OFF” will power down the TCU after the program; “HOLD” will
control the setpoint from the last segment after the program; “LOOP” will
continuously loop through the program; “SETP” will control at the setpoint prior to
the program.

4. Press the Enter button to accept the value.
5. Press the Alarm Silence button to return to Running mode.
6. Press the Run/Hold button to activate the program.