Air-Cooled Condenser – Aluminum fin/ tube with washable filters, packaged units only.
Variable speed fan control standard for all remote air cooled condensers and GPAC70
through 210. Optional on GPAC20 through 50.

Water-Cooled Condenser – Tube-in-tube condensers (GPWC20 – GPWC50), Shell-and-
tube condensers (GPWC70 – GPWC210). All come with electronic cooling water regulating
valves.

Remote Air-Cooled Condenser– Aluminum fin/tube with low ambient control down to
–20ºF (-29ºC) via variable-speed fan(s).

Reservoir – GP20 and GP30 models use a 20 gallon (75 liter) polyethylene tank, GP40 and
GP50 models use a 40 gallon (150 liter) polyethylene tank, GP70 thru GP105 models use a
70 gallon (265 liter) polyethylene tank, GP140 thru GP210 models use a 140 gallon (530
liter) polyethylene tank. 304SS is available as an option for all sizes.

Piping – Non-ferrous chilled water piping

Pump – ODP motors (TEFC Optional)—horizontally mounted stamped stainless steel
construction.

Other Mechanical Features

• Low process water thermal flow switch

• NEMA-rated fan motor(s) on air-cooled models

• Galvanized structural steel frame, polyester powder coat painted cabinetry

• Internal process water bypass valve for system protection only

• Fully insulated refrigeration and process water piping

• 20 mesh Y strainer on process water piping into the evaporator

• Tank level indication via operator interface

• Pump pressure indication via operator interface

Electrical Features

• Fully accessible NEMA 4/12-style electrical control enclosure

• Single-point power and ground connection

• Non-fused disconnect switch, lockable

• Branch circuit protection

• 208-230/3/60, 460/3/60, 575/3/60 volt; 400/3/50 volt

Refrigeration Features

• HFC-410a refrigerant

• Electronic modulating hot gas bypass capacity control

• High refrigerant pressure cutout switch (manual reset)

• Suction and discharge pressure transducers.

• High refrigerant pressure spring actuated relief valve

Advertising