Chapter 4: Operation

45 of 93

4-4 Access Levels

The controller is setup to allow access to three distinct password groups: operator, supervisor,
and service. Operator access allows the user to modify the Leaving Water Temp, Hi Temp
Warning, and Hi Temp Fault setpoints. Supervisor access allows the supervisor to modify the
above plus

Selecting any of the menus in the Menu Screen will display the Password Screen.

4-5 Controller Setpoints

Variable

Description

Access Level

Operator

Supervisor

Chilled Fluid SP

Temperature of chilled fluid out to process

x

x

Chil Hi Temp Wrn

Setpoint for alarm to warn when chilled leaving fluid
temperature is too high

x

x

Chil Hi Temp Flt

Setpoint to shut down pump and compressor based
on leaving fluid temperature

x

x

Process SP

Temperature of tempered fluid out to process

x

x

Proc Hi Temp Wrn

Setpoint for alarm to warn when tempered leaving
fluid temperature is too high

x

x

Proc Hi Temp Flt

Setpoint for alarm to warn when tempered leaving
fluid temperature is too high

x

x

Proc Low Temp Wrn

Setpoint for alarm to warn when tempered leaving
fluid temperature is too low

x

x

Proc Low Temp Flt

Setpoint for alarm to warn when tempered leaving
fluid temperature is too low

x

x

Cooling Enabled

Refrigeration system allowed to operate

x

Heating Enabled

Optional Process temperature heater allowed to
operate

x

Fluid Freeze Point

Lowest temperature fluid will operate without
freezing. Below 32°F (0°C) glycol must be added.
Forces lowest Chilled fluid setpoint to be 13°F (7°C)
above FFP

x

Chill On Diff

Temperature difference above chilled fluid setpoint
before compressor turns on

x

Chill Off Diff

Temperature difference below chilled fluid setpoint
before compressor turns off

x

Proc On Diff

Temperature difference below process setpoint
before process heater turns on

x

Proc Off Diff

Temperature difference above process setpoint
before process heater turns off

x

Proc Hi Temp Dly

Time (in seconds) Process High Temperature alarm
is ignored before activating

x