GP Series Portable Chillers

Chapter 3: Installation

33 of 93

Figure 11: Ethylene Glycol and Propylene Glycol Curves

Percent Glycol Curves for Freeze Protection

-60.0

-50.0

-40.0

-30.0

-20.0

-10.0

0.0

10.0

20.0

30.0

40.0

0.0

10.0

20.0

30.0

40.0

50.0

60.0

% Glycol by Volume

Ethylene Glycol

Propylene Glycol

Example: 45°F set point minus 20°F = 25°F.

From Figure 28, 25°F equates to 10% by volume of glycol required.

The standard pumps used in the GPAC Serice chillers are not recommended to
be used with fluid below 0°F (-18°C). Please consult factory for the proper
pump.