Chapter 3: Installation

24 of 93

• Refrigeration lines must not be crossed, i.e., chiller liquid lines are to be piped to

condenser liquid lines.

Sizing Refrigerant Lines. To determine field installed liquid and discharge line sizes, first
establish the equivalent length of pipe for each line, valve, and elbow. Chiller capacity and
leaving water temperature range is also required. See Figure 4 on page 24 for lengths of
refrigerant valves and fittings.

Liquid Line Sizing. The liquid line should be sized as small as possible while maintaining
acceptable pressure drop to minimize the refrigerant charge. Liquid line risers must not
exceed 15 feet from the base of the air-cooled condenser. Horizontal runs do not require a
pitch. Insulation is not required unless the line is installed in a high ambient area, i.e., boiler
room or on a roof. Install a liquid line-charging valve to facilitate refrigerant charging. See
Figure 5 on page 24 for sizing information. See Figure 7 on page 28 for charge determination.

Discharge Line Sizing. Discharge line sizing is based on the velocity required for sufficient
oil return back to the compressor. See Figure 4: Equivalent Length in Feet for Valves and
Fittings on page 27 for discharge line sizing.

For horizontal runs, the discharge line should be pitched downward, in the
direction of flow, at a rate of 1/2” for every 10 feet. This will allow oil to flow
towards the condenser.

Figure 4: Equivalent Length in Feet for Valves and Fittings

Line Size

OD (inches)

Angle

Valve

Short

Radius EL

Long

Radius EL

3/8

24

4

2.8

1/2

24

4.7

3.2

5/8

25

5.7

3.9

3/4

25

6.5

4.5

7/8

28

7.8

5.3

1-1/8

29

2.7

1.9

1-3/8

33

3.2

2.2

1-5/8

34

3.8

2.6

2-1/8

39

5.2

3.4

2-5/8

44

6.5

4.2

Figure 5: Liquid Line Sizing

GPRC-20

GPRC-30

Total Equiv.

Length (Ft)

Liquid Line Size (OD")

Total Equiv.

Length (Ft)

Liquid Line Size (OD")

Horizontal

or

Downflow

Upflow

1-5 Ft

Upflow

6-10 Ft

Upflow

11-15 Ft

Horizontal

or

Downflow

Upflow

1-5 Ft

Upflow

6-10 Ft

Upflow

11-15 Ft

25

1/2

1/2

1/2

1/2

25

5/8

5/8

5/8

5/8

50

1/2

1/2

1/2

1/2

50

5/8

5/8

5/8

5/8

75

1/2

1/2

1/2

1/2

75

5/8

5/8

5/8

5/8

100

1/2

1/2

1/2

5/8

100

5/8

5/8

5/8

5/8

125

1/2

1/2

1/2

5/8

125

5/8

5/8

5/8

5/8

150

1/2

1/2

5/8

5/8

150

5/8

5/8

5/8

5/8

175

1/2

5/8

5/8

5/8

175

5/8

5/8

5/8

3/4

200

1/2

5/8

5/8

5/8

200

5/8

5/8

5/8

3/4

225

1/2

5/8

5/8

5/8

225

5/8

5/8

5/8

3/4

250

5/8

5/8

5/8

5/8

250

5/8

5/8

3/4

3/4

275

5/8

5/8

5/8

5/8

275

5/8

5/8

3/4

3/4

300

5/8

5/8

5/8

5/8

300

5/8

5/8

3/4

3/4