GP Series Portable Chillers

Chapter 6: Troubleshooting

55 of 93

CC = Compressor Critical

SC = System Critical

PC = Process Critical

W = Warning

Alarm Name

#

Type

Possible Cause

Solution

Compressor Fault

1

CC

MCP Failure

Allow the compressor to cool

down. If the compressor does
not restart, disconnect power
and verify operation of the

MCP internal module. Replace
if necessary.

Compressor module has failed

Discharge Pressure Sensor Failure

2

W

Sensor Failure

Check the wiring connection at
the sensor, and at the controller.
If necessary replace sensor.

Electrical connection at
sensor open
Electrical connection at
controller open

Fan Overload

3

CC

Internal fan motor overload
tripped

Allow the fan to cool down. If
the fan does not restart when
called upon by controller,

replace fan motor.

VFD Fault

4

CC

Drive has detected internal
fault

Locate the drive and write
down the fault code shown on
the display of drive. Contact
customer service for assistance.

High Discharge Pressure Fault

5

CC

Dirty air cooled condenser or
inlet filter

Clean filter or condenser

Dirty water cooled condenser
or condenser valve failure

Clean condenser or verify
operation of condenser valve

Condenser fan overload

See Fan Overload Fault

Condenser fan VFD fault

See VFD Fault

Ambient air or condenser
water temperature too high

Verify supply temperature or air
removal capacity.

Too much refrigerant in

system.

Contact Customer Service for

assistance

Liquid line valves closed.

Verify operation of valve and
wiring on controller

Discharge pressure switch
failure

See Discharge Pressure Sensor
Failure

High Discharge Pressure Switch

6

CC

Dirty air cooled condenser or
inlet filter

Clean filter or condenser

Dirty water cooled condenser
or condenser valve failure

Clean condenser or verify
operation of condenser valve

Condenser fan overload

See Fan Overload Fault

Condenser fan VFD fault

See VFD Fault

Ambient air or condenser
water temperature too high

Verify supply temperature or air
removal capacity.

Too much refrigerant in

system.

Contact Customer Service for

assistance

Liquid line valves closed

Verify operation of valve and
wiring on controller

Discharge pressure switch

failure

See Discharge Pressure Sensor

Failure

High Suction Pressure Fault

7

CC

From Process fluid
temperature too high

Verify flow through system.
Make corrections as necessary.