GP Series Portable Chillers

Chapter 6: Troubleshooting

59 of 93

CC = Compressor Critical

SC = System Critical

PC = Process Critical

W = Warning

Alarm Name

#

Type

Possible Cause

Solution

Pump Flow Sensor Failure

34

W

Optional flow sensor failed

Verify wiring of flow sensor at
sensor and terminal block of
controller

Pump Pressure Sensor Failure

35

W

Sensor wires loose from
controller terminal block

Verify wiring of sensor at
sensor and terminal block of
controller

Sensor wires broke between
sensor and controller terminal
block.

Refrig Liquid Temp Sensor
Failure

36

W

Sensor wires loose from
controller terminal block

Verify wiring of sensor at
sensor and terminal block of
controller

Sensor wires broke between
sensor and controller terminal
block.

Refrig Suction Temp Sensor
Failure

37

W

Sensor wires loose from
controller terminal block

Verify wiring of sensor at
sensor and terminal block of
controller

Sensor wires broke between
sensor and controller terminal
block.

Tank Level Sensor Failure

38

W

Sensor wires loose from
controller terminal block

Verify wiring of sensor at
sensor and terminal block of
controller

Sensor wires broke between

sensor and controller terminal
block.

Water make-up failure

40

W

Make up solenoid failure

Verify wiring of solenoid valve
at valve and at terminal block.

Insufficient water pressure

Increase water pressure to be
above 5 psig (0.3 bar)

Auxilliary Alarm

41

SC/W

This alarm is configurable

Low Suction Pressure at Startup

42

CC

Parameter set too short for
remote condenser installation

Adjust parameter for length of
time to build suction pressure

Refrigerant amount too low

Contact Customer Service

For Units with a Tempered Loop

To ProcTemperature Sensor

Failure

43

PC

Loose or broken sensor wire

Verify wiring of temperature
sensor at sensor and terminal
block of controller

Process High Temp Fault

44

W

Process heater on

Verify heater contactor
operation

Process cooling valve off

Verify cooling valve operation

Process High Temp Warning

46

W

Process heater on

Verify heater contactor
operation

Process cooling valve off

Verify cooling valve operation

Process Low Temp Fault

48

W

Process heater off

Verify heater contactor
operation

Process cooling valve on

Verify cooling valve operation

Process Low Temp Warning

50

W

Process heater off

Verify heater contactor
operation

Process cooling valve on

Verify cooling valve operation

Pump 2 No Flow

52

SC/W

Optional process flow switch
failure

Verify operation of flow switch.

Process valves closed

Verify operation of process
valves and adjust as necessary