GP Series Portable Chillers

Chapter 6: Troubleshooting

60 of 93

CC = Compressor Critical

SC = System Critical

PC = Process Critical

W = Warning

Alarm Name

#

Type

Possible Cause

Solution

Pump 2 Overload

53

SC/W

Motor circuit protector open

Verify motor circuit protector
operation. Verify motor wiring
and amp draw while under load.

Pump flow rate in excess of
capacity

Verify system valves are
operational and properly set.
Contact customer service or

sales if pump is sized too small
for application.

High Temp Safety Switch

54

PC

Heater failure

Verify operation of heater and
cooling valve. .

Cooling Valve failure

Verify wiring at cooling valve
and at terminal bloc

Sensor failure

Replace sensor if necessary.

Phase Monitor Fault

55

SC

Unit wired incorrectly

Reverse two wires at line-side

of power switch on electrical
panel.

Loss of phase during

operation

Verify sensor wiring at sensor

and at terminal bloc.

Sensor failure

Replace sensor if necessary.

From Proc Sensor Failure

56

W

Sensor wires loose from
controller terminal block

Verify wiring at sensor and at
terminal block. y.

Sensor wires broke between
sensor and controller terminal

block.

Replace sensor if necessar

Non-Controller Related Issues

Problem

Possible cause

Solution

Unit does not run.

No power.

Check main disconnect, fuses, wiring,
and power lead to unit.

Wrong voltage supplied to unit.

Voltage must be within plus or minus
10% of nameplate rating.

Control circuit fuse blown.

Replace control circuit fuse.
Check transformer.
Check for a short circuit.

Defective control transformer.

Replace.

Piping flow switch circuit open.

Add water or water/glycol solution as
required.

Pump motor off on overload.

Reset and test.