SCW Series Central Chilling Stations

Figure 1

Typical Two-Circuit 60-195 Ton Water Cooled Chiller

SCWW-xxx

Model

60 75 90 100

Cooling Capacity (tons) @ 50°F LWT

c

60.4 74.9 88.8 102.2

Capacity stages

Infinite Unloading

EER (BTUH/W)

15.2 15.1 15.7 15.5

Evaporator

d

145 180 213 245

Nominal water flow (gpm)

Condensers

e

181 225 266 307

Condenser connection (no manifold) Flange Conn. (in.)

2.5

3

Evaporator manifold connection Victaulic

3

4

Amp draw, nameplate
(460/3/60 V)

f

Water-cooled

112 130 138 170

Height 85

74

Width 100

115

Dimensions (in.)

Depth 45

72

Shipping

weight

(lbs)

3,266 3,512 4,336 4,982

Max operating weight (lbs.)

3,468 3,754 4,594 5,246

c Based on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water.
d Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW).
e Based on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum.
f Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 1.2 for 380/3/60 amperages; multiply by 0.8 for

575/3/60 amperages

Advertising