10 installing the remote air-cooled condenser – Sterlco S Series Central Chilling Stations User Manual

Page 25

Advertising
background image

SCW Series Central Chilling Stations

Page 25 of 77

Two connections are made to each SCW Series unit:


Condenser Water In

The city or tower water supply inlet is located at the side or rear of
the chiller.
• Water pressure ≥ 25 psi (≥ 172.4 kPa/≥ 1.72 bars)
• Water temperature ≤ 85°F (≤ 29ºC)

Condenser Water Out

The return outlet, located at the chiller side or rear is connected to
a cooling tower inlet, a sewer or other approved discharge receiver.
• A water regulating valve is an optional feature in the

condenser water out line.

• Adjust the butterfly valve for the pressure drop that

corresponds to the model number of the chiller. Pressure drop
is equal to supply pressure minus return pressure. (If a water
regulating valve has been supplied, adjustment is not required.)

Water Side Pressure Drop

Condenser (each)

Evaporator (each)

Model

Number

Flow (gpm)

PD (psi)

Flow (gpm)

PD (psi)

SCWW/R60 91

4.0 72

5.3

SCWW/R75 102

4.7

90

4.5

SCWW/R90 117

4.4

107

5.6

SCWW/R100 150

5.5

123

3.9

SCWWR115 166

4.3

140

3.0

SCWW/R145 196

4.1

175

4.8

SCWW/R165 219

4.1

200

4.6

SCWW/R195 278

4.7

232

6.0

3-10 Installing the Remote Air-Cooled Condenser

SCW Series models use the surrounding air to cool the remote
condenser. All models have variable speed fans and low ambient
controls to allow proper operation down to -20°F (-29ºC) outdoor
air temperature.

Install the remote air cooled condenser where there is:

• Greater than or equal to -20°F (-29ºC) air temperature.
• Free passage of air for condensing.
• Adequate structural support.
• Protection from strong winds and drifting snow.
• Provisions for removal of heated air from the area.