8 high pressure cutout, 9 low pressure cutout, 10 flow switch – Sterlco S Series Central Chilling Stations User Manual

Page 31: Important

Advertising
background image

SCW Series Central Chilling Stations

Page 31 of 77

4-8 High Pressure Cutout

This electro-mechanical safety feature opens the control circuit if
the system condensing pressure exceeds a safe level.

High pressure cutout setting

Model psi

kPa

bars

SCW Series water-cooled and remote air-cooled
chilling stations

290 psi

2,000 kPa

20 bars

Important!

The high pressure cutout is a manual reset control,

so you should reset it once.

If the problem persists, call a refrigeration service technician

to analyze the problem and to reset the control.


4-9 Low Pressure Cutout

This encapsulated switch safety feature prevents the compressor
suction pressure from dropping below a pre-set point. It is factory
set to open the control circuit when pressure drops below a safe
level. The chiller will restart when the suction pressure reaches 30
psi (206.9 kPa/2.1 bars).

Opens control circuit @

Resets control circuit @

Model

psi kPa bars

psi kPa bars

SCW Series water-cooled and
remote air-cooled chilling stations

15 psi 103.4 kPa

1.0 bars 30 psi 206.9 kPa 2.1 bars


4-10 Flow Switch

The flow switch shuts down the chiller if the evaporator water flow
falls below a safe operating gallons-per-minute (liters-per-minute)
flow rate.