Caution – Sterlco S Series Central Chilling Stations User Manual

Page 30

Advertising
background image

Page 30 of 77

SCW Series Central Chilling Stations

If you want lower chilled water temperatures, you’ll need to mix
process water with industrial- (not automotive) grade ethylene or
propylene glycol with rust inhibitor to provide protection down to
20°F (12ºC) below the operating temperature you want. Figure 3
below shows the proper mixtures needed to provide protection to
20°F (12ºC) below the operating temperature you want. You can
then reset the freezestat cutout temperature to a temperature of
10°F (6ºC) below the operating temperature you selected.


Caution!

Make sure all freezestat adjustments are performed

by a qualified refrigeration service technician.

The Sterling product warranty does not cover system freeze-up!


Figure 3

Freezing Protection Curve

Ethylene glycol required for evaporator freeze protection

Ethylene

glycol

percent by

volume

Chilled water operating temperature ºF / ºC

60

50

40

30

20

10

0

-50ºF -40ºF

-40ºC

-30ºF -20ºF -10ºF 0ºF

10ºF 20ºF 30ºF 40ºF 50ºF 60ºF

16ºC

10ºC

4ºC

-1ºC

-7ºC

-12ºC

-18ºC

-23ºC

-29ºC

-34ºC

-46ºC

Advertising