11 checking motor direction, Check compressor rotation before starting unit – Sterlco S Series Central Chilling Stations User Manual

Page 26

Advertising
background image

Page 26 of 77

SCW Series Central Chilling Stations

• No steam, hot air or fume exhausts drawn into the condenser

coils.

• Service accessibility.

SCW Series condensing pressure

with 95ºF (35ºC) condenser air

R-134a = 171 psi (1,179 kPa/11.79 bars)

Note: Due to the variables involved in remote air-cooled condenser installations, no set or

standard piping procedure exists. Each installation must be designed and installed by
qualified persons. Follow the instructions supplied with the condenser.


3-11 Checking Motor Direction

Compressor

Check Compressor Rotation Before Starting Unit!

1. Connect a phase monitor and phase incoming power ABC.

2. Connect a refrigerant gauge to the suction service valve. Fully front seat

the service valve and open one full turn.

3. Bump start the compressor by switching off then on quickly 0.5 to 1

second. If the rotation is correct, the suction pressure will drop
immediately. A rise in pressure will indicate the wrong rotation. If this
occurs, change over two electrical phases of the incoming power supply
(do not change phase at the compressor starter).

Note:

• Never switch contactor leads or motor leads for reversing

rotation.

• Do not use contactor or motor leads for phase matching.
• Compressor damage will occur if the compressor is run in

reverse. The compressor motor protector checks for correct
phasing and will not allow it to start in reverse.

• If you discover that compressor rotation is reversed, correct it

by switching any two main power leads into the disconnect
switch or distribution block
on the unit.

Water Pump

A positive pressure of 20 to 30 psi (137.9 to 206.8 kPa/1.38 to 2.07
bars) on the

TO PROCESS

line indicates correct pump rotation.