Sterlco S Series Central Chilling Stations User Manual

Page 14

Advertising
background image

Page 14 of 77

SCW Series Central Chilling Stations

Figure 2

Typical Two-Circuit 60-195 Ton Remote Air Cooled Chiller

SCWR-xxx

Model

60 75 90 100

Cooling Capacity (tons) @ 50°F

LWT

53.8 67.1 79.1 91.2

Capacity stages

Infinite Unloading

EER

(BTUH/W)

9.4 9.9 9.8 10

Nominal

water

flow

(gpm)

Evaporator

129 161 190 219

Evaporator manifold connection Victaulic

3

4

No. of condenser fans per condenser

3

3

4

4

Chiller

112 130 138 170

Amp draw, nameplate
(460/3/60 V)

Condensers

(per

condenser)

11 11 14 14

Height 75

74

Width 100

115

Dimensions (in.) of chiller

Depth 45

72

Height 50
Width 45.5

45.5

Dimensions (in.) of each
condenser

Depth 180

235

Chiller

2,574 2,676 3,456 3,532

Shipping weight (lbs)

Condensers

(each

condenser)

1,190 1,210 1,580 1,620

Chiller

2,600 2,710 3,498 3,580

Max operating weight
(lbs.)

Condensers

1,215 1,240 1,650 1,660


SCWR-xxx

Model

115 145 165 195

Cooling Capacity (tons) @ 50°F

LWT

104.1 130.5 148.4 174.0

Capacity stages

Infinite Unloading

EER (BTUH/W)

10.3 10.5 10.4 10.2

Nominal water flow (gpm)

Evaporator

250 313 356 418

Evaporator manifold connection Victaulic

4

6

No. of condenser fans per condenser

4

5

6

8

Chiller

216 250 282 316

Amp draw, nameplate
(460/3/60 V)

Condensers (per condenser)

14

18

21

28

Height 77

81

Width 124

137

Dimensions (in.) of chiller

Depth 72

75

Height 50
Width 45.5

88

Dimensions (in.) of each
condenser

Depth

235 290 345 235

Chiller

4,156 7,528 7,554 7,698

Shipping weight (lbs)

Condensers (each condenser)

1,760

2,380

2,480

3,230

Chiller

4,212 7,788 7,814 8,016

Max operating weight
(lbs.)

Condensers (each condenser)

1,800

2,435

2,540

3,300

c Based on 50ºF (10ºC) chilled water supply temperature and 95ºF (35ºC) ambient air.
d Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW)
e Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 1.2 for 380/3/60 amperages; multiply by 0.8 for

575/3/60 amperages

Advertising