Scwr series remote condenser models – Sterlco S Series Central Chilling Stations User Manual
Page 15
SCW Series Central Chilling Stations
Page 15 of 77
SCWR Series Remote Condenser Models
Fan(s)
Refrigeration
d
Each Connections
Charge
Model Dia.
Motor Amps Air flow Discharge
Liquid
R-134a
Number in. hp
c
460V
Fans
cfm
e
ODS(in.) ODS(in.) lbs.
e
SCWR60
30 1 ½ hp 3 ø 11.0
3
34,800
21/8 21/8 19
SCWR75
30 1 ½ hp 3 ø 11.0
3
32,900
21/8 21/8 19
SCWR90
30 1 ½ hp 3 ø 14.0
4
46,400
21/8 21/8 22
SCWR100
30 1 ½ hp 3 ø 14.0
4
42,400
21/8 21/8 27
SCWR115
30 1 ½ hp 3 ø 14.0
4
41,500
21/8 21/8 27
SCWR145
30 1 ½ hp 3 ø 18.0
5
51,800
25/8 25/8 43
SCWR165
30 1 ½ hp 3 ø 21.0
6
65,800
25/8 25/8 50
SCWR195
30 1 ½ hp 3 ø 21.0
8
87,800
2 @ 21/8
2 @ 21/8 44
c ø represents electrical phase; all motors are 1,140 rpm. Multiply hp by 0.746 to convert to kW.