4.2 Timer state

4.2.1 Setting a timer output destination

The timer output can be connected to "control" or "event output (1-6)" to control "control" and
events 1 and 3 with the timer. It can thus be set to a desired setting.
In the case of "timer disabled," set the timer time to 0:00.


4.2.2 Setting a timer function

The options available are "auto start," "manual start," "event start," and "SV start."
(1) Auto start

The timer automatically begins to operate when it is turned on.

(2) Manual start

The timer starts when a function key or DI is set to timer start and its action is generated.

(3) Event start

The timer starts when either of the events in progress is activated.

(4) SV start

The timer starts when it is turned on and it goes beyond the SV value + the SV start tolerance
setting (for OFF delay only).


4.2.3 Setting a timer type

The options available are "inactivate timer," "ON delay," "OFF delay," and "repeat." After that,
the timer types will be described on the assumption that the timer function is set to "auto start."
(1) ON delay

Turning on the system starts it in a startup setting state. When a set time is up, control
begins.


ON delay

(control

stopped)

Normal

state

(control in

progress)

ON delay T.O.

Power

OFF

Power ON