46/66

Character

PV screen
Auxiliary screen

Designation

Description

Initial value

18

 ch


Set an AT
sensitivity

Thermocouple input
Setting range: 0 to 999 or 0.0 to 999.9
Setting unit:

°C

Resistance bulb input
Setting range: 0 to 999 or 0.0 to 999.9 or 0.00 to

999.99

(when the input type is, ,
or )

Setting unit:

°C

Current and voltage inputs
Setting range: 0 to 99999

The decimal place can be set to a
desired position.

Setting unit:

digit



CH2 only
Potentiometer input
Setting range: 0.0 to 999.9
Setting unit:

%

19

□ch


Set a proportional
band for the main
output

Setting range: 0.0 to 200.0
Setting unit: % of  ch to  ch



20

□□ch


Set an integration
time for the main
output

Setting range: 0 to 3,600 seconds

21

□□ch


Set a derivative
time for the main
output.

Setting range: 0 to 3,600 seconds

22

□ch


Set a proportional
cycle for the main
output

Setting range: 1 to 120 seconds



23

 ch


Anti-reset windup

Setting range: 0.0 to 100.0 (-10.0 to -110.0: in analog

output)

Setting unit: %



24

 ch


Set an upper limit
for the main output
operation amount
limiter

Setting range: Set a lower limit for the operation amount

limiter to 100.0 (-110.0: in analog output)

Setting unit: %



25

 ch


Set a lower limit
for the main output
operation amount

Setting range: Set the system to 0.0 (-10.0: in analog

output) to an upper limit for the operation
amount limiter

Setting unit: %



26

 ch


Manual reset

Setting range: 0.0 to 100.0

-100.0 to 100.0 (heating/cooling)

Setting unit: %

