5.5.6 80mm twin pipe flue system

Refer to the Atmos Price List for the full list of flue components.











Table of Atmos 80mm twin flue equivalent lengths

Terminal

The flue discharge at the terminal
must be at least 75mm in front of the
air intake and the distance between
the two pipes at least 75mm.

Maximum total length allowed is 60 metres

(ie Equivalent length of supply pipe + Equivalent length of flue discharge pipe) (Note: Includes

an allowance for the terminal; ie the terminal can be ignored from the equivalent length)

80mm components

Equivalent length (M)

Remarks

45

0

bend 1.5

87

0

bend 3.0

80mm Twin pipe extensions for balcony

outlet
When the free outlet is hindered by an eave,
balcony, gallery or anything else, the air supply

pipe and the flue discharge pipe must be

extended to at least the front side of the

overhanging part. (In this case the flue
discharge must be extended 75mm further than

the air supply pipe inlet).

When the air supply is not disturbed by

obstacles, such as a separating wall, and when
the outlet is not at the edge of a building, the air

supply pipe does not need extension (see

diagram).