Setting maximum ch power, Setting pump position – Atmos Energy HE26 User Manual

Page 38

Advertising
background image

7.4

Setting maximum CH power

The maximum CH power is set to 50% in the factory. When the CH
system requires more or less power, the maximum CH power can be

changed by adjusting the fan speed. See table: Setting CH power.
This table gives the relation between the fan speed and the appliance
power.

Setting CH power



























Press loss/pump lift (m head)

Flow (litres/hr)

Required CH power

Setting on service display

InterSystem HE26

(approx kW)

(% of the maximum speed)

26.2 83
23.5 75
21.9 70
20.4 65
18.9 60
17.4 55
15.8 50
14.2 45
12.7 40
11.1 35
9.5 30
8.0 25


Caution
The power slowly increases while burning (modulation by time) and
decreases as soon as the set supply temperature is reached.

7.5

Setting pump position

The switch for setting the pump position is located on the connecting box
of the CH pump
1. Set the pump position on the basis of the set maximum power and

the resistance of the system on the water side. See diagram:
Pressure loss and pump lift, type Ups 50-130, positions 1, 2 and 3.

2. Check the temperature difference between the supply and return of

the appliance: this should be about 20°C.

The minimum flow-through

Set power

200 l/h

7.0 kW

750 l/h

26.2 kW




A. (Not

applicable)

B. InterSystem

HE26

I Pump

position

1

II Pump

position

2

III Pump

position

3

X

Flow-through in litres/hr

Y

Pressure loss / pump lift in metres head


38