Reduced output, Ch does not reach the correct temperature – Atmos Energy HE26 User Manual

Page 45

Advertising
background image

8.5 Reduced output

Possible causes

Remedies

8.6 CH does not reach the correct temperature



Table 6. NTC resistances

NTC 12 kOhm

T [°C]

R[ohm]

T [°C]

R[ohm]

T [°C]

R[ohm]

-15 76020 25

12000 65

2752

-10

58880

30 9805

70 2337

-5 45950

35 8055

75 1994

0 36130

40 6653

80 1707

5 28600

45 5522

85 1467

10 22800

50 4609

90 1266

15 18300

55 3863

95 1096

20 14770

60 3253

100 952

1. Check appliance and flue system

At high speed, the power has decreased

Yes

by not more than 5%.

for pollution.

2. Clean appliance and flue system.

Possible causes

1. Check the setting and adjust if

Room thermostat settings not correct.

Yes

necessary: set to 0.1 A.

No

1. Raise the pump setting or replace

the pump.

1. Check for circulation: at least 2 or 3

radiators must be open.

1. Adjust the power,

see Setting maximum CH power.

1. Descale or flush the heat exchanger

on the CH side.

No heat transfer due to scaling or pollution

in the heat exchanger.

Yes

The boiler power is not set well

for the system.

Yes

No

No

No circulation in the system.

Yes

Pump does not run well.

Pump setting too low.

Yes

No

No

1. Raise the CH temperature,

Temperature set too low.

see CH operation.

Yes

2. Check the outside sensor for

short circuit: remedy this..

Remedies

45