8.3

Burner resonates

Possible causes

Remedies

8.4

No heating (CH)

1. The house gas meter may be faulty.

Inlet pressure too low.

Yes

Contact the gas company.

No

1. Check the adjustment,

see Gas-air control.

Gas-air mixture not adjusted properly.

Yes

1. Check the flue gases and air supply.

Re-circulation of the flue gases.

Yes

No

Possible causes

1. Check the wiring.

Room thermostat/weather-dependent

control not closed or faulty.

2. Replace the thermostat.

Yes

3. Replace the weather-dependent control.

No

1. Check the voltage.

2. Check the connector x4.

3. Replace defective pump.

4. Replace defective controller.

1. Replace sensor S1 or S2.

See Fault code display: 1 or 2.

1. See Burner does not ignite.

Burner does not ignite.

Yes

No

Burner does not operate on CH: -

Sensor S1 or S2 faulty.

Yes

Pump does not run.

Yes

No

1. Check the wiring according to the

No voltage (24 V).

diagram.

Yes

2. Check the connector x4.

3. Replace defective controller

No

Remedies

44