Parameters – Atmos Energy HE26 User Manual

Page 37

Advertising
background image

7.3

Parameters

Parameter Setting

Factory

setting

Description

InterSystem

HE 26

0 Service

code

[15]

-

Access to installer settings. The service code must be entered

(=15).

1

System type

1

0 = standard
1 = heating only operation + indirect hot water tank
(Note: Factory setting is 1. Do not change this setting)
2 = n/a
3 = n/a

2

CH pump continuous

0

0 = pump normal with overrun
1 = pump on continuously; 2 = n/a

3

Set CH power

50

Setting maximum CH load, range c – 99% (or 100 if button
pressed again when 99 reached)

4

Set max power

50

Setting maximum power (can be increased to 99)

5

Min. supply temperature of
the control line

25

Setting range 10°C to 25°C (Weather-dependent control)

6

Min. outside temperature of
the control line

-7

Setting range -9°C to 10°C (Weather-dependent control)

7

Max. outside temperature of
the control line

25

Setting range 10°C to 30°C (Weather-dependent control)

8

CH pump overrun time after

CH operation

1

Setting range 0 - 15 minutes

9

CH pump overrun time after

external HW tank operation

2

Setting range 0 - 15 minutes (n/a)

A

Position of three-way or two-

way valve

0

0 = output signal given for CH operation (n/a)

1 = output signal given for HW tank operation (n/a)

b (n/a)

C

Step modulation

1

0 = step modulation off during CH operation

1 = step modulation on during CH operation

c

Min speed in CH operation

25

Setting range 25 to 50% of fan speed (Note: For propane or

for appliances with flue non-return valve, set 40)

d (n/a)

E

Min. supply temperature

during OT demand

10

Setting range 10°C to 60°C. (OT = OpenTherm stat)

E.

OT response

0

0 = Ignore the OT demand if it is lower than parameter E

1 = Set the value at parameter E, if the OT demand is lower
2 = OT device is switched off and the room stat functions as
an on/off switch, with the supply temp set at the appliance.

F

Starting speed CH

70

Setting range 50 to 99% (Note: For propane, set 50).
This parameter sets the fan speed for ignition and post purge.

F.

Starting speed DHW
(not applicable to
InterSystem)

70

Setting range 50 to 99% (Note: For propane, set 50).
This parameter sets the fan speed for ignition and post purge

h

Max. fan speed

45

Setting range 40 to 50 (40 = 4000 rpm, 50 = 5000 rpm) The
absolute maximum speed can be set through this parameter.

n (n/a)

o

Heating delay after hw use

0

(n/a) (0 to 15 mins).

P

Minimum switch off time
during CH operation

5

Setting range 0 to 15 minutes (anti cycling function)


37