Installation instructions – GE GFDR480GFWW User Manual

Page 14

Advertising
background image

Installation Instructions

REQUIREMENTS FOR ALCOVE OR

CLOSET INSTALLATION

MOBILE OR MANUFACTURED HOME

INSTALLATION

14

- Explosion Hazard

WARNING

Keep flammable materials and vapors, such as gasoline,

away from dryer.
Place dryer at least 18” (46 cm) above the floor for a

garage installation.
Failure to do so can result in death, explosion, or fire.

Installation must conform to the

MANUFACTURED HOME CONSTRUCTION AND

SAFETY STANDARD, TITLE 24, PART 32–80 or

Standard CAN/CSA-Z240 MH, or, when such

standard is not applicable, with AMERICAN

NATIONAL STANDARD FOR MOBILE HOME,

ANSI/NFPA NO. 501B.

The dryer MUST be vented to the outdoors. The

exhaust vent must be securely fastened to a

non-combustible portion of the mobile home.

The vent MUST NOT be terminated beneath a

mobile or manufactured home.

The vent duct material MUST BE METAL.

KIT 14-D346-33 MUST be used to attach the dryer

securely to the structure.

The vent MUST NOT be connected to any other

duct, vent or chimney.

Do not use sheet metal screws or other

fastening devices which extend into the interior

of the exhaust vent.

Provide an opening with a free area of at least

25 square inches for introduction of outside air

into the dryer room.

See the sections for electrical connection

information.

If the dryer is approved for installation in an

alcove or closet, it will be stated on a label on the

dryer back.

The dryer MUST be vented to the outdoors.

Minimum clearance between dryer cabinet and

adjacent walls or other surfaces is:

0”

either

side

3”

front

3”

rear

1”

top

52” from floor to overhead cabinets

Consideration must be given to provide adequate

clearance for installation and service.

Closet ventilation openings required: 2 louvers

each 60 square inches (387 square cm), located 3

inches (7.6 cm) from top and bottom of door.

Gas Dryers Only:

No other fuel burning appliance shall be installed

in the same closet as a gas dryer.

The dryer must be disconnected from the gas

supply piping during pressure testing at pressures

greater than ½ psi (3.5 kPa).

A 1/8 inch NPT minimum plugged tapping,

accessible for test gauge connection, must be

installed immediately upstream of the gas supply

connection to the dryer.

Advertising