Operating environment, Measuring, Figure 29 – Vaisala DM70 User Manual

Page 64: Gas collection option, Caution

Advertising
background image

USER'S GUIDE____________________________________________________________________

0405-011

Figure 29

Gas Collection Option

The following numbers refer to Figure 29 above.

1

=

Gas from GIE

2

=

Gas to the collecting system

Operating Environment

A typical dewpoint of pure SF

6

is usually around -60 °C. The

recommendations for the moisture limit of the equipment insulated
with gas (GIE) vary between
70 ... 810 ppm

v

, which corresponds to -45 ... -22 °C T

d/f

in the

atmospheric pressure, or -29 ... -3 °C T

d/f

in 5 bar

g

pressure. DM70 is

able to measure the dewpoint directly in the GIE pressure (usually 3 ...
8 bar

g

), or the gas can be sampled and measured in the atmospheric

pressure. If there is a need to measure high-pressure gas (>10 bar), for
example in the recycling bottle, a regulator should be used to drop the
pressure before the measurement.

High-voltage equipment can locate either indoors or outdoors. The
operational temperature range of DM70 is between -10 ... +60 °C.

Measuring

CAUTION

Before measuring moisture, make sure that hydrofluoric (HF) acid is
not present in the GIE.

62 __________________________________________________________________ M010091EN-F