ARI Armaturen ARI-PREMIO User Manual

Page 19

Advertising
background image

0040501000 4511

Page 19

Operating and installation instructions

Thrust actuator ARI-PREMIO

5.3.2 Mounting for valve lift over 30 mm to 80 mm (column version)

Fig. 8
To mount the thrust actuator to a valve having a nominal lift of over 30mm to 50mm,
proceed as follows:

- Screw coupling (pos. 50.27) out of torsion safety feature (pos. 50.32) of thrust

actuator
(not illustrated).

- Position valve cone approximately in mid lift position.

Fig. A:

- Turn flat hexagon nut if not present on valve spindle.

Fig. A-B: - Slip coupling (pos. 50.27) over valve spindle.

- Screw threaded bush (pos. 50.87) matching the valve onto the valve spindle in

accordance with setting dimension (Y) and lock with hexagon nut.

- Setting dimension (Y) for fitting-projection (X) 83mm = 102mm.

- Setting dimension (Y) for fitting-projection (X) 98mm = 116mm.

ATTENTION !
Setting dimension (Y) and fitting-projection (X) are measured with
inserted valve spindle. This means for
- 2-way valves at closed valve,
- 3-way valves with mixing plug at closed way B,
- 3-way valves with diverting plug at closed way A
After measuring put the valve plug back in the mid lift position!

Hexagon nut

Valve spindle

Hexagon nut

Valve spindle

turn