Thrust actuator ARI-PREMIO

5.5.7 Electronic position indicator RI21

The electronic position indicator RI21 converts the resistance of the 1000 ohm
potentiometer corresponding to the lift into an optional output control signal 0 (2) ...10V DC
or 0 (4) ...20mA DC. For installing and setting the electronic position indicator RI21 the
operating instructions applicable to this unit must be observed in the appropriate valid
version. The corresponding operating instructions are supplied with each unit.

5.5.8 Electronic position controller ES11
The electronic position controller ES11 converts continuous input control signals 0 (2)
...10V DC or 0 (4) ...20mA into a 3-point output signal for the motor, in which case
interrogation of the valve position takes place via a 1000 ohm potentiometer. For installing
and setting the electronic position controller ES11 the operating instructions applicable to
this unit must be observed in the appropriate valid version. The corresponding operating
instructions are supplied with each unit.

Fig. 17: Installing RI21 / ES11 / heating ARI-PREMIO 2.2 - 5 kN

Pos.

Designation

Pos.

Designation

50.78/79

Option ES11 or RI21

50.82

Head cap screw
DIN EN ISO 4762 - M4x12

50.80

Holding bracket

50.83

Heating

50.81

Head cap screw
DIN EN ISO 4762 - M4x8