6 wiring diagram, 7 connection conditions, 6 wiring diagram 5.5.14.7 connection conditions – ARI Armaturen ARI-PREMIO User Manual

Page 49

Advertising
background image

0040501000 4511

Page 49

Operating and installation instructions

Thrust actuator ARI-PREMIO

5.5.14.6 Wiring diagram

Fig. 29

5.5.14.7 Connection conditions
The electrical connections are joined to position indicator RI32 by series disconnect
terminals. The connection to the potentiometer is made by a cable.
Position indicator RI32 is connected by a potentiometer (R1 or R2) built into the ARI-
PREMIO.
When the valve is shut approx. 0 ohm are applied between Rb and Rc.
Appropriate conductor cross-sections for terminal connections are 0.2 to 2.5 mm

2

.

To achieve electromagnetic compatibility is recommended that shielded conductors be
used for longer routings.
Please request technical information direct from ARI-Armaturen.

Attention:

Do not connect terminal 2 and
terminal 3.
With a potential shift, the position
indicator RI32 might be destroyed.

or

Potentiometer connection optionally

with R1 or R2 potentiometers

from 100 Ohm to 20 kOhm

Two-wire connection

(current loop)

4...20mA

24V DC

Four-wire connection

4...20mA

24V DC and AC

Four-wire connection

2...10V

24V DC and AC

Advertising