Thrust actuator ARI-PREMIO

9.0 Troubleshooting table

ATTENTION !
- read point 10.0 and 11.0 prior
to dismantling and repair work!
- read point 6.0 before restarting the plant !

Fault

Possible Causes

Remedy

Thrust actuator fails to move

Power failure

Ascertain and eliminate cause

Fuse has blown

Replace fuse

Thrust actuator not properly
connected

Rectify connection on thrust
actuator in accordance with wiring
diagram

Short circuit due to:

- moisture

Ascertain exact cause,

- Dry the thrust actuator and

eliminate leakage

- wrong connection

- Rectify connection on thrust

actuator in accordance with
wiring diagram

- motor has burned out

- Check whether the mains voltage

agrees with the voltage specified
on the rating plate. Have motor
changed.

Connector contacts not plugged in/
not properly plugged into jack strip

Insert connector firmly in jack strip
thus affected

(Only for 12 - 15 kN)

Handwheel is still engaged and

does not disengage when the

motor starts up

Unscrew the motor mounting

screw closest to the cable feed-

through. (Manual release of the

handwheel disengagement

mechanism.)

Thrust actuator alternates
between clockwise and
counter-clockwise rotation

Motor operating capacitor
defective

Have motor operating capacitor
replaced

Thrust actuator fails to run to
final positions and also
produces chatter

Load-dependent travel switches
out of

/ defective

Remove thrust actuator and send
to factory for repair

Voltage drop due to excessively
long connecting cables or
inadequate conductor cross-
section

Lay connecting cables in
accordance with requisite output

Mains fluctuations beyond
permissible tolerance travels

Arrange for "clean" mains system
within requisite tolerances

System pressure too high

Reduce system pressure

Periodic failure on thrust
actuator

Loose connection on feedline

Tighten connections on terminal
strips

Thrust actuator is switched off
in retracting direction prior to
load-dependent switch (three-
way valve)

Travel switch S3 not set
corresponding to use

Set travel switch S3 in accordance
with operating instructions