SR Series Inverter

22

Menu

Status

Buzzer

Message

Power ON or Push Keypad

ON

Alert

FAN Fail or UV Alarm or Overload Alarm ON

Shutdown

OVP or UVP or OLP or OTP

ON

Disable

Any

OFF

4).

Alert Setup: When alert occurs, the internal Dry Contact Relay will

open / close. (See details in Section 3-1-6)

Default= Alert, SHDN

Setting Range= Disable / Shutdown / Alert / Alert, SHDN

Menu

Status

Relay

Alert

FAN Fail or UV Alarm or Overload Alarm

ON

Shutdown

OVP or UVP or OLP or OTP

ON

Disable

Any

OFF

5-3-2.

I/P Parameter (Select Menu):

6).

OVP Setting: Sets the Over Voltage Protection (OVP) and shutdown.

Default= 34 VDC for 24 V Model, 60 VDC for 48 V Model

Model

Setting Value Range

24 V

30 VDC ~ 34 VDC

48 V

60 VDC MAX.

7).

OVP Recovery: When the DC input voltage is higher than the OVP

setting, the inverter shuts-down; Once the input voltage

falls below the set OVP value, the inverter will

automatically restart.

Default= 30 VDC for 24 V Model, 56VDC for 48 V Model

Model

Setting Value Range

24 V

28 VDC ~ 32 VDC

48 V

56 VDC ~ 60 VDC

8).

UVP Setting: Setting the inverter’s Under Voltage Protection (UVP) and

Shutdown.

Default= 18 VDC for 24 V Model, 36 VDC for 48 V Model

Model

Setting Value Range

24 V

18 VDC ~ 22 VDC

48 V

36 VDC ~ 44 VDC

9).

UVP Recovery

:

When the DC input voltage is below the set UVP value

the inverter shuts-down; Once the input voltage rises

above the set UVP value, the inverter will automatically

restart.

Default= 25 VDC for 24 V Model, 50 VDC for 48 V Model