Model, 24 v, 97 vac ~ 123 vac – Samlex America SR1000-148 User Manual

Page 24: 47 hz ~ 63 hz, Sr series inverter

Advertising
background image

SR Series Inverter

23

Model

Setting Value Range

24 V

23 VDC ~ 27 VDC

48 V

46 VDC ~ 54 VDC

10). UV Alarm: Sets Under Voltage (UV) alarm. When the input voltage is

lower than the set value, the unit will sound “beep” to remind

that the unit is going to shutdown. At the meantime, the
contact in the internal Dry Contact Relay will open / close
(See details in Section 3-1-6).
Default= 21 VDC for 24 V Model, 42 VDC for 48 V Model

Model

Setting Value Range

24 V

19 VDC ~ 23 VDC

48 V

38 VDC ~ 46 VDC

NOTE. The value of voltage set for the “UV Alarm” should be equal to or

higher than the value set for “UVP” or else the unit will shutdown
without any audible warning.

5-3-3. O/P Parameters:

11). O/P Voltage: Set the inverter output voltage.

Default= 110 VAC for 110 V Model, 230 VAC for 220 V Model

Model

Setting Value Range

110 V

97 VAC ~ 123 VAC

220 V

194 VAC ~ 246 VAC

12). O/P Frequency: Set the inverter output frequency.

Default= 60 Hz for 110 V Model, 50 Hz for 220 V Model.

Model

Setting Value Range

110 V

47 Hz ~ 63 Hz

220 V

47 Hz ~ 63 Hz

13). Sync Frequency: Sets the AC output synchronous frequency.

Example: AC input= 230 VAC / 50Hz,User setting Value= 7Hz

When the DC to AC inverter “Frequency” is

within The Range of 43 Hz~57 Hz, the internal
bypass relay will

operate normally. When the

“Frequency” is less than 43 Hz or more than 58 Hz,

the internal bypass relay will de-energize.
(See details in Section 2-2)
Default= 0.1Hz ~ 7Hz.

Model

Setting Value Range

110 V

0.1 Hz ~ 7 Hz

230 V

0.1 Hz ~ 7 Hz