Sr series inverter – Samlex America SR1000-148 User Manual

Page 6

Advertising
background image

SR Series Inverter

5

RS-232 communication.

Dry contact terminal.

Efficiency >90%. (Full linear load at 220VAC Output)

Advanced Protection Features:

Input over/under voltage protection.

Internal over temperature protection.

Input reverse polarity protection (Fuse).

Output overload protection.

Output short circuit protection

AC input short circuit protection: Breaker (6 Amp or 12 Amp)

2-2. Block Diagram

AC GRID

INPUT

DC

INPUT

FILTER

DC

DC

AC

DC

FILTER

AC

OUTPUT

BYPASS RELAY

The inverter features IGBT technology which, minimizes weight and dimension,
while enhancing output short circuit reliability and overload capacity.

AC output voltage is provided in one of the two following modes:

1). From DC to AC Inverter Mode: (On-line Mode)

2). From AC Input Bypass Mode: (Off-line Mode)

Either mode is front panel programmable.
In the first option, Off-line mode, AC output power will be supplied through the AC
bypass mode in its normal operation. Upon AC input failure, output power will be
diverted through the DC to AC Inverter Mode. Once AC mains are restored, the unit
will revert from the Inverter Mode to the Bypass Mode.

In the second option, On-line mode, AC output power will be provided directly by
the inverter from the DC source. Should the DC source or inverter fail, the system
will transfer its output power through the bypass mode. Once the DC power source
is restored, the system will revert to the inverter mode.