Rack mounting assembly instructions – Avaya IP OFFICE 40DHB0002USCL User Manual

Page 42

Advertising
background image

Page 42 - Initial Assembly

Installing a New System

Rack Mounting Assembly Instructions

IP403, 406, 412 and expansion modules can be mounted in any standard 19" rack as follows:



CAUTIONS: Elevated Operating Ambient Temperature:

If installed in a closed or multi-unit rack assemble, the operating ambient temperature

of the rack environment may be greater that the room ambient. Therefore,

consideration should be given to installing the equipment in an environment

compatible with the manufacturer’s maximum rated ambient temperature (Tmra).

Reduced Air Flow:

Installation of the equipment in a rack should be such that the amount of air flow

required for safe operation of the equipment is not compromised.

Mechanical Loading:

Mounting of the equipment in the rack should be such that a hazardous condition is

not achieved due to uneven mechanical loading.

Circuit Overloading:

Consideration should be given to the connection of the equipment to the supply circuit

and the effect that overloading of circuits might have on overcurrent protection and

supply wiring. Appropriate consideration of equipment nameplate ratings should be

used when addressing this concern.

Reliable

Grounding:

Reliable grounding of rack-mounted equipment should be maintained. Particular

attention should be given to supply connections other than direct connections to the

branch circuit (e.g. use of power strips). See page 37.

Page 42 - Installing a New System

IP Office Installation Manual

Initial Assembly

40DHB0002USCL – Issue 7 (09/25/2002)