– 5 –

Sub Trunk line 1

PS24

PS24

PS24

PS24

PS24

Sub station

NHR-3TS

6(3P)

To the farthest sub,
max.165' (50m) with
min. 22AWG wire.
Sub trunk line must not
exceed 330' (100m) in
total with 22AWG wire.

10

9

5

8

7

6

3

3

3

3

6(3P)

3

NHR-3TS

6(3P)

Sub Trunk lines 2 ~ 8

PS-24E or PS-2420

16' (5m)

w/18AWG

165' (50m) w/18AWG

65' (20m)

w/22AWG min.

65' (20m)

w/22AWG min.

65' (20m) w/ 22AWG

6(3P)

5

5

5

5

5

6(3P)

10(5P)

65' (20m)

w/22AWG min.

NHR-4A

NHR-3A-4
(up to 4)

Do not connect two power supplies in parallel.

NHX-80X

CCU

Zone lights

NHR-SP

Duty station

NHX-50M &
NHX-30G

Master & Add-on

Staff call
area

Common area
Restrooms

Bedside sub
area (multiple
stations)

Bedside sub
area (single
station)

(*) Each zone requires a separate common wire

from the NHX-80X.

(*)4P with
NHR-3A-4

(*)4P with
NHR-3A-4

(*)4P with
NHR-3A-4

(*)4P with
NHR-3A-4

NHR-7A

Bathroom pullcord

NHR-7A

(common)

NH-1SA/A

(4 units)

NHR-8A

NHR-8A

NHR-7A

NHR-7A

2

3

3

6(3P)

NHR-4A

(*)4P with
NHR-3A-4

NHR-7A

NH-1SA/A

NH-1SA

NHR-8A

1

3

3

NHR-4A

NHR-7A

NH-2SA/A

NH-2SA

Junction box

1. SYSTEM OUTLINE & COMPONENTS