Alto-Shaam ASF-75G User Manual

Page 8

Advertising
background image

V E N T I L A T I O N

1.

A single ASF-75G or ASF-60G auto-lift gas fryer
requires a minimum of 120 CFM make-up air for
natural gas and 48 CFM for propane gas. Kitchen
ventilation must be of sufficient capacity to prevent a
negative-pressure condition. DO NOT obstruct or
restrict ventilation nor the air flow required to support
combustion.

2.

DO NOT

obstruct the flow of the exhaust flue at the

top rear of the fryer. It is especially critical that gas
supply piping and electrical support cord and/or
receptacle be routed away from the path of the hot
combustion fumes.

3.

This fryer cannot be direct vented.

4.

Install the fryer under a ventilation hood meeting all
applicable code requirements. Combustion fumes
must be vented in accordance with local, state, or
national codes.

An adequate ventilation system is required for commercial cooking equipment. Information may be obtained by writing
to the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. When writing refer to NFPA No. 96.

D A N G E R

Installation, air adjustment and/or
service work must be in accordance
with all local codes and must be
performed by a certified service
technician qualified to work on
gas appliances.

C A U T I O N

To prevent malfunction or cause
negative back draft, DO NOT obstruct
exhaust flues or attach any flue
extension that will impede proper
burner operation.

I N S T A L L A T I O N

Gas Fryer Operation & Care Manual • 7

D A N G E R

FAILURE TO VENT THIS FRYER PROPERLY

MAY BE HAZARDOUS TO THE

HEALTH OF THE OPERATOR.

Equipment damage and operational problems

may also be the consequence of improper venting.

Any damages sustained by a failure to properly

vent this fryer are not covered under warranty.

Ventilating hoods and exhaust systems shall be permitted to be
used to vent appliances installed in commercial applications.

Where automatically operated appliances are vented through a
ventilating hood or exhaust system equipped with a damper or
with a power means of exhaust, provisions shall be made to allow
the flow of gas to the main burners only when the damper is open
to a position to properly vent the appliance and when the power
means of exhaust is in operation.

IN ACCORDANCE WITH

NFPA 54

COMMONWEALTH OF MASSACHUSETTS ONLY

.

Advertising
This manual is related to the following products: