© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Installation

F232085

28

Do not connect the ground to the neutral (N-white
wire) leg at the power input block terminal strip. Refer
to Figure 12.

If a delta supply system is used, the high leg must be
connected to L3 (red wire) at the power input block. If
three-phase service is not available and a phase adder
is used, the artificial leg must be connected to L3.
Refer to Figure 12.

Figure 12

Refer to Figure 13 for the terminal strip for Design 5.

Figure 13

P039I

1

Power Input Block

2

Ground Lug: Connect to proven earth ground

P039I

2

1

N
White

S (L2)
Blue

R (L1)
Black

DESIGNS 1-4

T (L3)
Red

P037I

1

Ground Lug: Connect to proven earth ground

2

Power Input Block

1

DESIGN 5

(L1)

R

Black

(L2)

S

Blue

(L3)

T

Red

Connections to
Control Module

2