4.9.

IP20 & IP66 (Nema 4X) Non- Switched UnitsDrive & Motor Connections

For 1 phase supply power should be connected to L1/L, L2/N. For 3 phase supplies power should be connected to L1, L2, L3. Phase sequence is
not important. The Motor should be connected to U, V, W
For drives that have a dynamic brake transistor an optional external braking resistor will need be connected to +DC and BR when required.
The brake resistor circuit should be protected by a suitable thermal protection circuit. The –DC, +DC and BR connections are blanked off by
plastic tabs when sent from the factory. The plastic tabs can be removed if/when required.
Size 1 Connections

IP20

IP66 (Nema 4X)

Size 2 & 3 Connections

IP20

IP66 (Nema 4X)


4.10.

Using the REV/0/FWD Selector Switch (Switched Version Only)

By adjusting the parameter settings the drive can be configured for multiple applications and not just for Forward or Reverse.
This could typically be for Hand/Off/Auto applications (also known and Local/Remote) for HVAC and pumping industries.

Switch Position

Parameters to Set

Notes

P-12

P-15

Run Reverse

STOP

Run Forward

0

0

Factory Default Configuration
Run Forward or Reverse with speed controlled from the
Local POT

STOP

STOP

Run Forward

0

5,7

Run forward with speed controlled form the local POT
Run Reverse - disabled

Preset Speed 1

STOP

Run Forward

0

1

Run Forward with speed controlled from the Local POT
Preset Speed 1 provides a ‘Jog’ Speed set in P-20

Run Reverse

STOP

Run Forward

0

6, 8

Run Forward or Reverse with speed controlled from the
Local POT

Run in Auto

STOP

Run in Hand

0

4

Run in Hand – Speed controlled from the Local POT
Run in Auto 0 Speed controlled using Analog input 2 e.g.
from PLC with 4-20mA signal.

Run in Speed Control

STOP

Run in PI Control

5

1

In Speed Control the speed is controlled from the Local
POT
In PI Control, Local POT controls PI set point

Run in Preset Speed

Control

STOP

Run in PI Control

5

0, 2, 4,5,

8..12

In Preset Speed Control, P-20 sets the Preset Speed
In PI Control, POT can control the PI set point
(P-44=1)

Run in Hand

STOP

Run in Auto

3

6

Hand – speed controlled from the Local POT
Auto – Speed Reference from Modbus

Run in Hand

STOP

Run in Auto

3

3

Hand – Speed reference from Preset Speed 1 (P-20)
Auto – Speed Reference from Modbus

NOTE

To be able to adjust parameter P-15, extended menu access must be set in P-14 (default value is 101)