E 28, Technical data, Environmental – Beijer Electronics Industrial Inverter E2 User Manual

Page 28: Rating tables

Advertising
background image

28

9. Technical Data

9.1. Environmental

Operational ambient temperature range

Open Drives:

-10 … 50°C (frost and condensation free)

Enclosed Drives:

-10 ... 40°C (frost and condensation free)

Storage ambient temperature range:

-40 … 60°C

Maximum altitude:

2000m. Derate above 1000m : 1% / 100m

Maximum humidity:

95%, non-condensing

NOTE

For UL compliance: the average ambient temperature over a 24 hour period for 200-240V, 2.2kW and 3HP drives is 45°C.

9.2. Rating Tables

110 - 115 Volt (+ / - 10%) 1 Phase Input, 3 Phase 230V Output

Frame

size

Power

rating

Nominal

Fuse

Supply

Nominal

Motor

Maximum

Recommended

Input

Or

Cable

Output

Cable

Motor

Brake

Current

MCB (Type B)

Size

Current

Size

Cable

Resistance

[kW]

[A]

Non UL

UL

[mm2]

AWG / kcmil

[A]

[mm2]

AWG / kcmil

Length [m]

Ω

1

0.37

11.0

16

15

2.5

14

2.3

1.5

14

50

-

1

0.75

19.0

25

25

4

10

4.3

1.5

14

50

-

2

1.1

25.0

32

35

6

8

5.8

1.5

14

100

50


200 - 240 Volt (+ / - 10%) 1 Phase Input, 3 Phase Output

Frame

size

Power

rating

Nominal

Fuse

Supply

Nominal

Motor

Maximum

Recommended

Input

Or

Cable

Output

Cable

Motor

Brake

Current

MCB (Type B)

Size

Current

Size

Cable

Resistance

[kW]

[A]

Non UL

UL

[mm2]

AWG / kcmil

[A]

[mm2]

AWG / kcmil

Length [m]

Ω

1

0.37

5.0

10

10

1.5

14

2.3

1.5

14

50

-

1

0.75

8.5

10

10

1.5

14

4.3

1.5

14

50

-

1

1.5

13.9

16

20

2.5

12

7

1.5

14

50

-

2

1.5

13.9

16

20

2.5

12

7

1.5

14

100

100

2

2.2

19.5

25

25

4

10

10.5

1.5

14

100

50


200 - 240 Volt (+ / - 10%) 3 Phase Input, 3 Phase Output

Frame

size

Power
rating

Nominal

Fuse

Supply

Nominal

Motor

Maximum

Recommended

Input

Or

Cable

Output

Cable

Motor

Brake

Current

MCB (Type B)

Size

Current

Size

Cable

Resistance

[kW]

[A]

Non UL

UL

[mm2] AWG / kcmil

[A]

[mm2] AWG / kcmil

Length [m]

Ω

1

0.37

3.0

6

6

1.5

14

2.3

1.5

14

50

-

1

0.75

4.5

6

6

1.5

14

4.3

1.5

14

50

-

1

1.5

7.3

10

10

1.5

14

7

1.5

14

50

-

2

1.5

7.3

10

10

1.5

14

7

1.5

14

100

100

2

2.2

11.0

16

15

2.5

12

10.5

1.5

14

100

50

3

4

18.8

20

20

4

10

18

2.5

10

100

50


380 - 480 Volt (+ / - 10%) 3 Phase Input, 3 Phase Output

Frame

size

Power

rating

Nominal

Fuse

Supply

Nominal

Motor

Maximum

Recommended

Input

Or

Cable

Output

Cable

Motor

Brake

Current

MCB (Type B)

Size

Current

Size

Cable

Resistance

[kW]

[A]

Non UL

UL

[mm2]

AWG / kcmil

[A]

[mm2]

AWG / kcmil

Length [m]

Ω

1

0.75

2.4

6

6

1.5

14

2.2

1.5

14

25

-

1

1.5

4.3

6

10

1.5

14

4.1

1.5

14

25

-

2

1.5

4.3

6

10

1.5

14

4.1

1.5

14

50

200

2

2.2

6.1

10

10

1.5

14

5.8

1.5

14

50

200

2

4

9.8

16

15

2.5

12

9.5

1.5

14

50

100

3

5.5

14.6

20

20

4

10

14

1.5

12

100

100

3

7.5

18.1

25

25

4

10

18

2.5

10

100

50

3

11

24.7

32

35

10

8

24

4

10

100

50


Note

: For UL compliance, Motor Cable to be 75°C Copper, fuse current ratings in brackets (), UL Class T must be used.