User pi control mode, Motor thermistor connection, 26 7.4. user pi control mode – Beijer Electronics Industrial Inverter E2 User Manual

Page 26

Advertising
background image

26

7.4. User PI Control Mode

P-15

Digital input 1 (T2)

Digital input 2 (T3)

Digital input 3 (T4)

Analog input (T6)

Comments

0, 2,

9..12

Open: Stop (disable)
Closed: Run (enable)

Open : PI control
Closed : Preset speed 1

PI feedback analog input

Analog input 1

Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1

1

Open: Stop (disable)
Closed: Run (enable)

Open : PI control
Closed : Analog input 1

PI feedback analog input

Analog input 1

Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1

3, 7

1)

Open: Stop (disable)
Closed: Run (enable)

Open : PI control
Closed : Preset speed 1

External trip input :
Open: Trip, Closed: Run

PI feedback analog input

Connect external thermistor
type PT100 or similar to
digital input 3

4

Normally Open (NO)
Momentary close to run

Normally Closed (NC)
Momentary open to stop

PI Feedback Analog Input

Analog Input 1

Normally Open (NO)
Momentary close to run

5

Normally Open (NO)
Momentary close to run

Normally Closed (NC)
Momentary open to stop

Open: PI Control
Closed: Preset Speed 1

PI Feedback Analog Input

Normally Open (NO)
Momentary close to run

6

Normally Open (NO)
Momentary close to run

Normally Closed (NC)
Momentary open to stop

Open: External Trip
Closed: Run

PI Feedback Analog Input

Normally Open (NO)
Momentary close to run

8

Open: Stop (disable)
Closed: Run (enable)

Open : Forward run
Closed : Reverse run

PI feedback analog input

Analog input 1

Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1


Example Wiring

PI Mode P-12=5, P-15=0

PI Mode P-12=5, P-15=1

PI Mode P-12=5, P-15=3

+24 Volt

+24 Volt

+24 Volt

Run (Enable)

Run (Enable)

Run (Enable)

PI / Preset Speed 1

PI / Local (Hand)

PI / Preset Speed 1

PI Feedback

PI Feedback

External Trip

+10 Volt

Local (Hand) Ref

PI Feedback

0 Volt

0 Volt

0 Volt

Remote closed loop PI feedback control

with Local Preset speed 1

Remote closed loop PI feedback control with

Local Analog speed input

Remote closed loop PI feedback control with

Local Preset speed 1 and motor thermistor

trip

NOTE

By default the PI reference is set for a digital reference level set in P-45.
When using an Analog reference set P-44 = 1 (analog) and connect reference signal to analog input 1 (T6).
The default settings for proportional gain (P-41), integral gain (P-42) and feedback mode (P-43) are suitable for most HVAC and pumping
applications.
The analog reference used for PI controller can also be used as the local speed reference when P15=1.


7.5.

Motor Thermistor Connection

1 : + 24 Volt

The motor thermistor should be connected between terminals 1 and 4 as shown. A
setting of P-15 where Digital Input 3 is programmed for ‘External Trip’ must be used.
The current flow through the thermistor is automatically controlled to prevent a
failure.

4 : External Trip