Keypad mode (p-12 = 1 or 2), Modbus control mode (p-12 = 4) – Beijer Electronics Industrial Inverter E2 User Manual

Page 25

Advertising
background image

25

Terminal Mode P-12=0, P-15=3

Terminal Mode P-12=0, P-15=4

Terminal Mode P-12=0, P-15=11

+24 Volt

+24 Volt

+24 Volt

Run (Enable)

Run (Enable)

Run Forward

Analog / Preset 1

Local / Remote
(Hand / Auto)

Stop

External Trip

Remote (Auto)
Reference

Run Reverse

+ 10 Volts

+ 10 Volts

+ 10 Volts

Reference

Local (Hand)
Reference

Reference

0 Volts

0 Volts

0 Volts

Analog speed input with 1 preset speed

and motor thermistor trip

Local or remote analog speeds

(2 analog inputs)

Push button fwd/rev/stop with fast stop

using 2

nd

deceleration ramp

7.2. Keypad Mode (P-12 = 1 or 2)

P-15

Digital input 1 (T2)

Digital input 2 (T3)

Digital input 3 (T4)

Analog input (T6)

Comments

0, 1,

5,

8..12

Open: Stop (disable)
Closed: Run (enable)

Closed : remote UP push-
button

Closed : remote DOWN
push-button

Open : Forward
+24V : Reverse

2

Open: Stop (disable)
Closed: Run (enable)

Closed : remote UP push-
button

Closed : remote DOWN
push-button

Open : Keypad speed ref
+24V : Preset speed 1

3

1)

Open: Stop (disable)
Closed: Run (enable)

Closed : remote UP push-
button

External trip input :
Open: Trip, Closed: Run

Closed : remote DOWN
push-button

Connect external thermistor
type PT100 or similar to
digital input 3

4

Open: Stop (disable)
Closed: Run (enable)

Closed : remote UP push-
button

Open : Keypad speed ref
Closed : Analog input 1

Analog input 1

6

1)

Open: Stop (disable)
Closed: Run (enable)

Open : Forward run
Closed : Reverse run

External trip input :
Open: Trip, Closed: Run

Open : Keypad speed ref
+24V : Preset speed 1

Connect external thermistor
type PT100 or similar to
digital input 3

7

Open: Forward Stop
Closed: Forward Run

Open: Reverse Stop
Closed: Reverse Run

External trip input :
Open: Trip, Closed: Run

Open : Keypad speed ref
+24V : Preset speed 1

Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)

Example Wiring

Keypad Mode P-12=1 or 2, P-15=0

+24 Volt

Run (Enable)

Increase Speed

Reduce Speed

+ 10 Volts

Forward / Reverse

0 Volts

Remote push button speed control with fwd/rev

NOTE

By default if the enable signal is present the drive will not Enable until the START button is pressed. To automatically enable the drive when the
enable signal is present set P-31 = 2 or 3. This then disables the use of the START & STOP buttons

7.3. Modbus Control Mode (P-12 = 4)

P-15 Digital input 1 (T2)

Digital input 2 (T3)

Digital input 3 (T4)

Analog input (T6)

Comments

0..2,
4..5,

8..12

Open: Stop (disable)
Closed: Run (enable)

No effect

No effect

No effect

Run and stop commands
given via the RS485 link and
Digital input 1 must be closed
for the drive to run.

3

1)

Open: Stop (disable)
Closed: Run (enable)

Open : Master speed ref
Closed : Preset speed 1

External trip input :
Open: Trip, Closed: Run

No effect

Connect external thermistor
type PT100 or similar to
digital input 3

6

1)

Open: Stop (disable)
Closed: Run (enable)

Open : Master speed ref
Closed : Analog input

External trip input :
Open: Trip, Closed: Run

Analog input reference

Master Speed Ref - start and
stop controlled via RS485.
Keypad Speed Ref - drive
auto runs if digital input 1
closed, depending on P-31
setting

7

1)

Open: Stop (disable)
Closed: Run (enable)

Open : Master speed ref
Closed : keypad speed ref

External trip input :
Open: Trip, Closed: Run

No effect

For further information on the MODBUS RTU Register Map information and communication setup; please contact us.