7. Analog and Digital Input Configurations

7.1. Terminal Mode (P-12 = 0)

P-15

Digital input 1 (T2)

Digital input 2 (T3)

Digital input 3 (T4)

Analog input (T6)

Comments

0

Open: Stop (disable)
Closed: Run (enable)

Open : Forward run
Closed : Reverse run

Open : Analog speed ref
Closed : Preset speed 1

Analog input 1 reference

1

Open: Stop (disable)
Closed: Run (enable)

Open: Analog speed ref
Closed : Preset speed 1/2

Open: Preset speed 1
Closed : Preset speed 2

Analog input 1 reference

2

Open: Stop (disable)
Closed: Run (enable)

Digital Input 2

Digital Input 3

Preset Speed

Open: Preset speeds 1-4
Closed : Max Speed(P-01)

4 Preset speeds selectable.
Analog input used as digital
input Closed status: 8V < Vin
< 30V

Open

Open

Preset Speed 1

Closed

Open

Preset Speed 2

Open

Closed

Preset Speed 3

Closed

Closed

Preset Speed 4

3

Open: Stop (disable)
Closed: Run (enable)

Open : Analog speed ref
Closed : Preset speed 1

External trip input :
Open: Trip,
Closed: Run

Analog input 1 reference

Connect external thermistor
type PT100 or similar to
digital input 3

4

Open: Stop (disable)
Closed: Run (enable)

Open : Analog input 1
Closed : Analog input 2

Analog input 2 reference Analog input 1 reference

Switches between analog
inputs 1 and 2

5

Open: Fwd Stop
Closed: Fwd Run

Open: Reverse Stop
Closed: Reverse Run

Open : Analog speed ref
Closed : Preset speed 1

Analog input 1 reference

Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)

6

Open: Stop (disable)
Closed: Run (enable)

Open : Forward
Closed : Reverse

External trip input :
Open: Trip,
Closed: Run

Analog input 1 reference

Connect external thermistor
type PT100 or similar to
digital input 3

7

Open: Stop (disable)
Closed: Fwd Run (enable)

Open: Stop (disable)
Closed: Rev Run (enable)

External trip input :
Open: Trip,
Closed: Run

Analog input 1 reference

Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)

8

Open: Stop (disable)
Closed: Run (enable)

Open : Forward
Closed : Reverse

Digital Input 3

Analog Input 1

Preset Speed

Open

Open

Preset Speed 1

Closed

Open

Preset Speed 2

Open

Closed

Preset Speed 3

Closed

Closed

Preset Speed 4

9

Open: Stop (disable)
Closed: Forward Run
(enable)

Open: Stop (disable)
Closed: Reverse Run
(enable)

Digital Input 3

Analog Input 1

Preset Speed

Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)

Open

Open

Preset Speed 1

Closed

Open

Preset Speed 2

Open

Closed

Preset Speed 3

Closed

Closed

Preset Speed 4

10

Normally Open (NO)
Momentary close to run

Normally Closed (NC)
Momentary open to stop

Open : Analog speed ref
Closed:Preset speed 1

Analog input 1 reference

11

Normally Open (NO)
Momentary close to run

Normally Closed (NC)
Momentary open to stop

Normally Open (NO)
Momentary close to rev

Analog input 1 reference

Closing digital inputs 1 and 3
together carries out a fast
stop (P-24)

12

Open: Stop (disable)
Closed: Run (enable)

Open: Fast Stop (disable)
Closed: Run (enable)

Open : Analog speed ref
Closed : Preset speed 1

Analog input 1 reference

NOTE

Negative Preset Speeds will be inverted if Run Reverse selected


Typical Applications

Terminal Mode P-12=0, P-15=0

Terminal Mode P-12=0, P-15 = 1

Terminal Mode P-12=0, P-15=2

+24 Volt

+24 Volt

+24 Volt

Run (Enable)

Run (Enable)

Run (Enable)

For / Rev

Analog / Preset

Preset Speeds 1 – 4
Select

Analog / Preset

Preset1 / Preset2

+ 10 Volts

+ 10 Volts

Reference

Reference

Preset / Max

0 Volts

0 Volts

Analog speed input with 1 preset speed and

fwd/rev switch

Analog speed input with 2 preset speeds

4 preset speeds and max speed select switch.

Effectively giving 5 preset speeds