6.4. P-00 Read Only Status Parameters

Description

Display range

Explanation



1st Analog input value

0 … 100%

100% = max input voltage



2nd Analog input value

0 … 100%

100% = max input voltage



Speed reference input

-P-01 … P-01

Displayed in Hz if P-10 = 0, otherwise displayed in RPM



Digital input status

Binary value

Drive digital input status



Reserved

0

Reserved



Reserved

0

Reserved



Applied motor voltage

0 … 600V AC

Value of RMS voltage applied to motor



DC bus voltage

0 … 1000V dc

Internal DC bus voltage



Internal Heatsink temperature

-20 … 100 °C

Temperature of heatsink in

°

C



Hours run meter

0 to 99 999 hours

Not affected by resetting factory default parameters



Run time since last trip (1)

0 to 99 999 hours

Run-time clock stopped by drive disable (or trip), reset on next
enable only if a trip occurred. Reset also on next enable after a
drive power down.



Run time since last trip (2)

0 to 99 999 hours

Run-time clock stopped by drive disable (or trip), reset on next
enable only if a trip occurred (under-volts not considered a trip)
– not reset by power down / power up cycling unless a trip
occurred prior to power down



Run time since last disable

0 to 99 999 hours

Run-time clock stopped on drive disable, value reset on next
enable



Drive Effective Switching
Frequency

4 to 32 kHz

Actual drive effective output switching frequency. This value
maybe lower than the selected frequency in P-17 if the drive is
too hot. The drive will automatically reduce the switching
frequency to prevent an over temperature trip and maintain
operation.



DC bus voltage log

0 … 1000V

8 most recent values prior to trip, updated every 250ms



Thermistor temperature log

-20 … 120 °C

8 most recent values prior to trip, updated every 500ms



Motor current

0 to 2x rated
current

8 most recent values prior to trip, updated every 250ms



Software ID, IO & motor ctrl

e.g. “1.00”, “47AE”

Version number and checksum.
“1” on LH side indicates I/O processor,
“2“ indicates motor control



Drive serial number

000000 … 999999
00-000 … 99-999

Unique drive serial number
e.g. 540102 / 32 / 005



Drive identifier

Drive rating

Drive rating, drive type
e.g. 0.37, 1 230,3P-out

Parameter group zero access and navigation

When P-14 = P-37, all P-00 parameters are visible. Default value is 101.

When the user scrolls to P-00, pressing

will display “

XX

”, where

XX

represents the secondary number within P-00. (i.e. 1 to 20).

The User can then scroll to the required P-00 parameter.

Pressing

once more will then display the value of that particular group zero parameter.

For those parameters which have multiple values (e.g. software ID), pressing the

and

keys will display the different values within that

parameter.

Pressing

returns to the next level up. If

is then pressed again (without pressing

or ), the display changes to the next level up

(main parameter level, i.e. P-00).
If

or is pressed whilst on the lower level (e.g. P00-05) to change the P-00 index, pressing <NAVIGATE> quickly displays that parameter