Vent Piping Guidelines

This gas furnace can be installed as either a Non-Direct

Vent or a Direct Vent gas central furnace.

NOTE: In non-Direct Vent installations, combustion air is

taken from indoors and flue gases are discharged outdoors.

In Direct Vent installations, combustion air is taken from

outdoors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing - Size pipe according to Tables

4 and 5. Table 4 lists the minimum vent pipe lengths

permitted. Table 5 lists the maximum pipe lengths permitted.

Regardless of the diameter of pipe used, the standard roof

and wall terminations described in section Exhaust Piping

Terminations should be used. Exhaust vent termination pipe

is sized to optimize the velocity of the exhaust gas as it exits

the termination. Refer to Table 6.

In some applications which permit the use of several different

sizes of vent pipe, a combination vent pipe may be used.

Contact Allied Air Technical Service for assistance in sizing

vent pipe in these applications.

NOTE: The exhaust collar on all models is sized to

accommodate 2” Schedule 40 vent pipe. When vent pipe

which is larger than 2” must be used in an upflow application,

a transition must be applied at the exhaust collar in order to

properly step to the larger diameter vent pipe. Contact Allied

Air Technical Service for more information concerning sizing

of vent systems which include multiple pipe sizes.

Do not use screens or perforated metal in exhaust or

intake terminations. Doing so will cause freeze-ups and

may block the terminations.

IMPORTANT

NOTE: All horizontal runs of exhaust pipe must slope back toward

unit. A minimum of 1/4” (6 mm) drop for each 12” (305 mm) of

horizontal run is mandatory for drainage.

NOTE: Exhaust pipe MUST be glued to furnace exhaust fittings.

NOTE: Exhaust piping should be checked carefully to make sure

there are no sages or low spots.

EXHAUST PIPE

Horizontal Application

Figure 20

Use the following steps to correctly size vent pipe diameter.

*Any approved termination may be added to the minimum length
listed.
**This gas furnace must have 3" to 2" reducing ell (supplied or field
replacement Canadian kit) installed directly into unit flue collar.

MINIMUM VENT PIPE LENGTHS