3. If exhaust piping must be run up a sidewall to position

above snow accumulation or other obstructions, piping

must be supported every 24” (610 mm) as shown in

Figure 39. When exhaust piping must be run up an

outside wall, any reduction in exhaust pipe size must be

done after the final elbow.

Condensate Piping

This unit is designed for either right or left side exit of

condensate piping in upflow applications. In horizontal

applications, the condensate trap must extend below the

unit. An 8” service clearance is required for the condensate

trap. Refer to Figure 41 for condensate trap locations.

NON-DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

Figure 37

NON-DIRECT VENT FIELD SUPPLIED WALL

TERMINATION

Figure 38

NON-DIRECT VENT FIELD SUPPLIED WALL

TERMINATION EXTENDED OR (15F74)

WALL TERMINATION VENT PIPE EXTENDED

Figure 39

* Use wall support every 24” (610 mm). Use two supports if extension

is greater than 24” but less than 48”.

NON-DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

NOTE: Do not discharge exhaust gases directly into any chimney or

vent stack. If vertical discharge through an existing unused chimney

or stack is required. Insert piping inside chimney until the pipe open

end is above top of the chimney and terminates as illustrated. In any

exterior portion of chimney, the exhaust vent must be insulated.

Figure 40