5. On field supplied terminations for sidewall exit, exhaust

piping may extend a maximum of 12 inches (305 mm)

for 2” PVC and 20 inches (508 mm) for 3” (76 mm) PVC

beyond the outside wall. Intake piping should be as

short as possible. See Figures 31 and 32.

6. On field supplied terminations, a minimum distance

between the end of the exhaust pipe and the end of the

intake pipe without a termination elbow is 8” and a

minimum distance of 6” with a termination elbow. See

Figures 31 and 32.

7. If intake and exhaust piping must be run up a side wall

to position above snow accumulation or other

obstructions, piping must be supported every 24” (610

mm) as shown in Figures 31 and 32. When exhaust

and intake piping must be run up an with pipe sized per

Table 6. The intake piping may be equipped with a 90°

elbow turndown. Using turndown will add 5 feet (1.5 m)

to the equivalent length of the pipe.

8. A multiple furnace installation may use a group of up to

four terminations assembled together horizontally, as

shown in Figure 35.

See venting Table 5 for maximum venting lengths with this

arrangement.

* Use wall support every 24” (610 mm). Use two wall supports if

extension is greater than 24” (610 mm) but less than 48” (1219 mm).

NOTE: One wall support must be 6” (152 mm) from top of each pipe

(intake and exhaust).

FIELD SUPPLIED WALL TERMINATION

Figure 32

DIRECT VENT CONCENTRIC ROOFTOP TERMINATION

71M80, 69M29 or 60L46 (US)

41W92 or 41W93 (Canada)

Figure 33