Allied Air Enterprises 92G1UH User Manual

Page 8

Advertising
background image

506501-01

Page 8 of 48

Issue 1031

Air from Outside

If air from outside is brought in for combustion and ventilation,

the confined space shall be provided with two permanent

openings. One opening shall be within 12” (305 mm) of the

top of the enclosure and one within 12” (305 mm) of the

bottom. These openings must communicate directly or by

ducts with the outdoors or spaces (crawl or attic) that freely

communicate with the outdoors or indirectly through vertical

ducts. Each opening shall have a minimum free area of 1

square inch per 4,000 Btu (645 mm² per .59 kW) per total

input rating of all equipment in the enclosure (See Figure 5).

If air from outside is brought in for combustion and ventilation,

the confined space must have two permanent openings. One

opening shall be within 12 inches (305 mm) of the top of the

enclosure and one opening within 12 inches (305 mm) of

the bottom. These openings must communicate directly or

by ducts with the outdoors or spaces (crawl or attic) that

freely communicate with the outdoors or indirectly through

vertical ducts. Each opening shall have a minimum free

area of 1 square inch (645 mm²) per 4,000 Btu (1.17 kW)

per hour of total input rating of all equipment in the enclosure.

See Figures 5 and 6. When communicating with the

outdoors through horizontal ducts, each opening shall have

a minimum free area of 1 square inch (645 mm²) per 2,000

Btu (.56 kW) per total input rating of all equipment in the

enclosure. See Figure 7.

When ducts are used, they shall be of the same cross-

sectional area as the free area of the openings to which

they connect. The minimum dimension of rectangular air

ducts shall be no less than 3 inches (75 mm). In calculating

free area, the blocking effect of louvers, grilles, or screens

must be considered. If the design and free area of protective

covering is not known for calculating the size opening

required, it may be assumed that wood louvers will have 20

to 25 percent free area and metal louvers and grilles will

have 60 to 75 percent free area. Louvers and grilles must

be fixed in the open position or interlocked with the equipment

so that they are opened automatically during equipment

operation.

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)

NOTE: The inlet and outlet air openings shall each have a free area

of at least one square inch per 4,000 Btu (645 mm² per 1.17 kW) per

hour of the total input rating of all equipment in the enclosure.

Figure 5

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

(Inlet Air through Ventilated Attic)

NOTE: The inlet and outlet air openings shall each have a free area

of at least one square inch per 4,000 Btu (645 mm² per 1.17 kW) per

hour of the total input rating of all equipment in the enclosure.

Figure 6

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

NOTE: Each air duct opening shall have a free area of at least one

square inch per 2,000 Btu (645 mm² per .59 kW) per hour of the

total input rating of all equipment in the enclosure. If the equipment

room is located against an outside wall and the air openings

communicate directly with the outdoors, each opening shall have a

free area of at least 1 square inch per 4,000 Btu (645 mm² per 1.17

kW) per hour of the total input rating of all other equipment in the

enclosure.

Figure 7

Advertising
This manual is related to the following products: