Connecting an In-Situ Instrument to the Computer

1

Laptop or PC

2

TROLL

®

Com Communication Device*

3

RuggedCable

®

System**

4

In-Situ instrument

* TROLL Com device may be a USB-connect, serial-connect, or direct-connect** model

** RuggedCable is omitted when using a direct-connect TROLL Com

Instrument Communication Settings

1. Connect to the instrument using Win-Situ 5 software.

2. Click the Device Setup tab

.

3. Click Modbus Setup...

4. Select the following options:

Baud: 9600
Data Bits: 8
Parity Bits: None
Stop Bits: 1
End Of Message Timeout (ms): 1000
End of Session Timeout (ms): 5000
Mode: Modbus-ASCII

5. Click the Checkmark. Click Yes to change the communication settings. Click Yes or

No to save these settings as the default for Win-Situ 5.

You must change Win-Situ Software communication settings to
match the instrument communication settings next time you
connect the instrument. Change Win-Situ settings under
Preferences > Comm Settings.

Set up and start a log in the instrument if you require data redundancy and your
instrument supports internal data logging.